© 2011 | Bachmann electronic GmbH Print page now

Analog Input / Output Modules

GIO212

GIO212

Universal Input/Output Module

  • Number of in- and outputs: 12 (analog und digital)
  • Resolution: input 16 Bit, output 14 Bit
  • Input voltage: to ±10 mV
  • Input current: 0(4) to 20 mA
  • Digital input 24 V
  • Digital 32-bit counter
  • Digital output 100 mA
  • Filter from 4 kHz to 0.5 Hz
  • Temperature sensor Pt 2-,3-,4-wire
  • Thermoelements J, K, T, N, E, R, S, B
  • Galvanic isolation from system: 500 V
  • Condensation-proof ColdClimate design

AIO208, AIO216

AIO208, AIO216

Universal Input/Output Modules

  • Number of in- and outputs: 8 (AIO208) / 16 (AIO216)
  • Resolution: input 16 Bit, output 14 Bit
  • Input voltage: ±10 V to ±10 mV
  • Input current: 0(4) to 20 mA
  • Filter from 4 kHz to 0.5 Hz
  • Temperature sensor Pt 2-,3-,4-wire
  • Thermoelements J, K, T, N, E, R, S, B
  • Galvanic isolation from system: 500 V
  • Condensation-proof ColdClimate design

AIO208/SI, AIO204/SI, AIO202/SI

AIO208/SI, AIO204/SI, AIO202/SI

Universal Input/Output Modules

  • 8 channels AIO208/SI, 4 channels AIO204/SI, 2 channels AIO202/SI
  • Analog inputs or outputs
  • Galvanically isolated by channel
  • Modes that can be selected per channel:

    • Analog voltage input ±10 V to 100 mV
    • Analog current input 4 to 20 mA, ±20 mA
    • Temperature sensor Pt elements as 2-,3-,4-wire
    • Thermoelements type J, K, T, N, E, R, S, B
    • Analog voltage output ±10 V
    • Analog current output 0(4) to 20 mA

  • Resolution: input 16 bits, output 14 bits
  • Filter adjustable from 4 kHz to 1 Hz per channel
  • All outputs overload, short circuit and external voltage-proof
  • Measuring range monitoring freely adjustable
  • Error message on overload and overtemperature, undervoltage in the supply unit
  • Galvanic isolation channel to channel and system 500 V

AI202/SI, AI204/SI

AI202/SI, AI204/SI

Analog Input Modules

  • Number of inputs: 2 / 8
  • Input current: 0 to 20 mA
  • Differential inputs
  • Resolution: 13 to 16 bit
  • Galvanic isolation from system: 500 V
  • Galvanic isolation of channels: 500 V  

AI208/SI

AI208/SI

Analog Input Modules

  • Number of inputs: 8
  • Input current: 4 to 20 mA, 0 to 20 mA, -20 to +20 mA
  • Resolution: 13 to 16 Bit
  • Galvanic isolation from system: 500 V
  • Galvanic isolation of channels: 500 V


AI204/x

AI204/x

Analog Input Modules

  • Number of inputs: 1 / 2 / 4
  • Input voltage: ±10 V DC
  • Differential inputs
  • Resolution: 16 bit
  • Inputs can be synchronized
  • Galvanic isolation from system: 500 V
  • Galvanic isolation of channels: 500 V  

AO202

AO202

Analog Output Module

  • Number of outputs: 2 
  • Output voltage: ±10 V DC
  • Differential and short circuit proof outputs
  • Resolution: 16 bit
  • Outputs can be synchronized
  • Galvanic isolation from system: 500 V
  • Galvanic isolation of channels: 500 V

 

 


AO202/SI, AO204/SI

AO202/SI, AO204/SI

Analog Output Modules

  • Number of outputs: 2 / 4
  • Output current: 0 to 20 mA  
  • Differential outputs
  • Short circuit proof outputs
  • Resolution: 16 bit
  • Galvanic isolation from system: 500 V  
  • Galvanic isolation of channels: 500 V  

AIO288/x

AIO288/x

Analog Input/Output Modules

  • Number of inputs:
  • 8 (±10 V DC / ±1 V DC or 0 to 20 mA)
  • Number of outputs: 8 (±10 V DC)
  • Resolution: 14 bit
  • Connection: single-ended or differential
  • Number of Pt100/Pt1000 sensors: 4
  • Connection: 2- or 4-wire technology
  • Optional galvanic isolation from system: 500 V

PTAI216

PTAI216

Temperature Recording Module

  • Number of inputs: 4 (±10 V DC  / ±1 V DC or 0 to 20 mA)
  • Connection: single-ended or differential
  • Resolution: 14 bit at AI
  • Number of Pt100/Pt1000 sensors: 12
  • Connection: 2-wire technology
  • Resolution: 12 bits with Pt100/Pt1000
  • Galvanic isolation from system: 500 V

TI214/x

TI214/x

Temperature Recording Module

  • TI214: 14 inputs for Pt100 / Pt1000 sensors as well as type J or K thermocouples
  • TI214/2: thermal couples type N or S
  • Resolution 14 bit (16 bit with measured value filtering)
  • Wire break detection on the measurement inputs
  • Galvanic isolation from system: 500 V

DMS202

DMS202

Strain Gauge Input Module

  • Number of strain gauge measuring inputs: 2 (full bridge)
  • Industrial connectors (LEMO)
  • Analog measuring outputs: 2
  • Automatic measuring range selection
  • Wire break detection on the measurement inputs
  • Resolution: 12 bit
  • Galvanic isolation from system: 500 V

AIC214

AIC214

Vibration Sensor Input Module

  • 12 analog inputs with IEPE interface for Piezo vibration sensors and up to 3 with ±10 V DC
  • 2 counter inputs or one incremental interface
  • Resolution: 24 bit AD resolution
  • Dynamics: ≥ 95 dB
  • Sampling rate up to 51.2 kHz; adjustable

AIC206

AIC206

Vibration Sensor Input Module

  • 4 analog inputs with IEPE interface for Piezo vibration sensors
  • 2 counter inputs or one incremental interface
  • Resolution: 24 bit AD resolution
  • Dynamics: ≥ 95 dB
  • Sampling rate up to 51.2 kHz; adjustable